IO-Digital8 sensor with 8 ALARM/NORMAL indication in the AKCP securityProbe 5E web interface. Can have 8 dry contacts on one Intelligent Sensor port. The main housing can be mounted on a wall and a standard CAT5 cable can be run to the intelligent sensor port on the securityProbe 5E.
There are two versions of the IO-digital8 depending on your requirements.
The first version has a single RJ45 connector at one end and 8 x 2 pin dry contact connectors along one side.
The second unit also has a single RJ45 connector at one end but the 8 x 2 pin dry contact connectors are replaced by two RJ45 connectors, each compatible with 4 dry contacts.
The dry contacts can be configured as inputs or outputs and the IO-digital8 is user definable so can be used to detect many different inputs such as UPS status, security systems, alarm panels or air conditioning status.
Specifications
Specifications
Measurement Range
Input: Alarm or Normal
Output : Set or Reset
Sensor Type
Input : Open / Closed contact switch
Output : High (5V) / Low (GND)
Contact voltage range
5 volts pulled-up dry contacts*
Input Measurement Rate
Multiple readings every second
Normal input state is settable under software on each of the 8 dry contacts
Electrical Output
Normally open, normally closed is settable under software on each of the 8 dry contacts
Can sink up to 20mA** on each of the 8 dry contacts ( when set to Low )
Interface
Communications Cable
RJ-45 jack to sensor using UTP Cat 5 wire
Communications Cable Max. length
RJ45 jack to sensor using UTP Cat 5 wire, Maximum extension cable length 305m (1000 ft.) with approved low capacitance shielded cable or UTP
Power Source
Powered by the sensorProbe+ or securityProbe+. No additional power needed
Full autosense including disconnect alarm
Important Note
*Dry Contacts are not isolated, don’t connect any voltage source
** Dry contact output is not suitable for direcly driving a relay
Sensor count
8
Features
SNMP interface for alarm/normal status
SNMP traps sent when critical
SNMP polling via get command
When an alarm condition is activated the description and location of the fault can be sent via email, SMS, MMS, Skype, phone calls and other advanced notifications from the securityProbe 5E’s web interface
Each of the 8 dry contacts on the IO-digital8 sensor can also be configured as outputs either 0 VDC or 5 VDC and can sink up to 20 mA of current when connected to a load