Enviromon

Wireless Sensors

sensorProbe+ Wireless Tunnel

Rapid deployment of your sensor network over large area

The sensorProbe+ Wireless Tunnel™ (SP-WT) is equipped with Semtech’s LoRa based radio technology, and utilizes the AKCP Wireless Tunnel™ communications protocol. Connect up to 4 wired sensors to a single radio. This makes for rapid deployment for a large number of sensors.

Connect up to 30 SP-WT devices to the sensorProbe+ Wireless Tunnel™ Server (SP-WTS), with 4 sensors on each that gives 120 sensors from only 30 radios. The SP-WT is powered by either 3x AAA batteries, or 5VDC USB input. Both can be used with the batteries as a failover power source. It is recommended where possible to power the SP-WT via external power supply. An optional external battery pack (SP-WT-EXTBAT) is also available for increased life of up to 10 years.

Features

  • Guaranteed message delivery
  • Proprietary AKCP Wireless Tunnel™ Protocol
  • Long range radio communications (up to 3km in open space)
  • Low power radio for extended battery life (sensor dependent)
  • Internal antenna tuned for greater signal strength
  • Plugin AKCP Intelligent sensors

Limitation of supported sensors:

  1. Dry contact:
    Input and output, input processed in IRQ,
    Not recommended for battery operation.
  2. Motion Detector:
    Processed in IRQ,
    Not recommended for battery operation.
  3. Water Detector
    Processed in IRQ,
    (at the moment)
    Not recommended for battery operation.
  4. Security Switch:
    Processed in IRQ,
    Not recommended for battery operation.
  5. Voltage Detector:
    Processed in IRQ,
    Not recommended for battery operation.
  6. Smoke Detector:
    Processed in IRQ,
    Not recommended for battery operation.
    No autosense, only onlined manually.
  7. DC5 (5x Dry Contacts):
    Processed in IRQ,
    Not recommended for battery operation.
    No autosense, only onlined manually.
    Only one per SP-WT used on Sensor Port #4.
  8. Pulse Counter:
    Processed in fast IRQ (frequency from 1Hz to 30KHz),
    Not recommended for battery operation.
    No autosense, only onlined manually.
    Only one sensor per SP-WT.
  9. ADC current 4..20 mA
    Processed in polling cycle,
    No autosense, can not be onlined manually.
    Supported only in SPWT-A2D (SP-WT with A2D input option).
  10. ADC voltage 0..10 V
    Processed in polling cycle,
    No autosense, only onlined manually.
    Supported only in SPWT-A2D (SP-WT with A2D input option).
  11. VC00
    Processed in polling cycle,
    Uses internal ADC to measure current 4-20 mA.
    Can not be onlined manually.
  12. IODC8
    Support input and output independently for each dry contact.
    Processed in fast polling cycle (1 Hz),
    Not recommended for battery operation.
    Could be autosensed and onlined only on port #1 and port #2.
  13. TDPS
    Processed in polling cycle.
    Not recommended for battery operation.